Monitor your Uninterruptible Power Supplies (UPS) over SNMP.
Monitor UPS health and battery status to prevent outages and ensure infrastructure reliability.
This extensions collects important UPS infrastructure metrics to monitor the health and reliability of devices. Metrics are collected through SNMP get polling.
Simply activate the extension in your environment using the in-product Hub, provide the necessary device configuration and you’re all set up.
The extension package contains:
The following SNMP MIB files are used for monitoring:
When activating your extension using monitoring configuration, you can limit monitoring to one of the feature sets. To work properly the extension has to collect at least one metric after the activation.
In highly segmented networks, feature sets can reflect the segments of your environment. Then, when you create a monitoring configuration, you can select a feature set and a corresponding ActiveGate group that can connect to this particular segment.
All metrics that aren't categorized into any feature set are considered to be the default and are always reported.
A metric inherits the feature set of a subgroup, which in turn inherits the feature set of a group. Also, the feature set defined on the metric level overrides the feature set defined on the subgroup level, which in turn overrides the feature set defined on the group level.
| Metric name | Metric key | Description |
|---|---|---|
| UPS Line Input Frequency | snmp.ups.line.InputFrequency | The present input frequency (0.1 Hertz). |
| UPS Line Input Voltage | snmp.ups.line.InputVoltage | The magnitude of the present input voltage (RMS Volts). |
| UPS Line Input Current | snmp.ups.line.InputCurrent | The magnitude of the present input current (0.1 RMS AMP) |
| UPS Line Input True Power | snmp.ups.line.InputTruePower | The magnitude of the present input true power (Watts). |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Line Output Voltage | snmp.ups.line.OutputVoltage | The present output voltage (RMS Volts). |
| UPS Line Output Current | snmp.ups.line.OutputCurrent | The present output current (0.1 RMS AMPS). |
| UPS Line Output Power | snmp.ups.line.OutputPower | The present output true power (WATTS). |
| UPS Line Output Percent Load | snmp.ups.line.OutputPercentLoad | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Battery Status | snmp.ups.BatteryStatus | The indication of the capacity remaining in the UPS system's batteries - unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) |
| UPS Seconds On Battery | snmp.ups.SecondsOnBattery | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power. |
| UPS Estimated Minutes Remaining | snmp.ups.EstimatedMinutesRemaining | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. |
| UPS Estimated Charge Remaining | snmp.ups.EstimatedChargeRemaining | An estimate of the battery charge remaining expressed as a percent of full charge. |
| UPS Battery Voltage | snmp.ups.BatteryVoltage | The magnitude of the present battery voltage (0.1 Volt DC). |
| UPS Battery Current | snmp.ups.BatteryCurrent | The present battery current (0.1 Amp DC). |
| UPS Battery Temperature | snmp.ups.BatteryTemperature | The ambient temperature at or near the UPS Battery casing (degrees Centigrade). |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Input Line Bads | snmp.ups.InputLineBads.count | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. |
| UPS Input Num Lines | snmp.ups.InputNumLines | The number of input lines utilized in this device. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Alarm Time | snmp.ups.alarm.AlarmTime | The value of sysUpTime when the alarm condition was detected. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS sys Up Time | snmp.ups.sysUpTime | The time (in hundredths of a second) since the network management portion of the system was last re-initialized. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Line Bypass Voltage | snmp.ups.line.BypassVoltage | The present bypass voltage (RMS Volts). |
| UPS Line Bypass Current | snmp.ups.line.BypassCurrent | The present bypass current (0.1 RMS AMPS). |
| UPS Line Bypass Power | snmp.ups.line.BypassPower | The present true power conveyed by the bypass (WATTS). |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Bypass Frequency | snmp.ups.BypassFrequency | The present bypass frequency (0.1 Hertz). |
| UPS Bypass Num Lines | snmp.ups.BypassNumLines | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Output Frequency | snmp.ups.OutputFrequency | The present output frequency (0.1 Hertz). |
| UPS Output Num Lines | snmp.ups.OutputNumLines | The number of output lines utilized in this device. This variable indicates the number of rows in the output table. |
| Metric name | Metric key | Description |
|---|---|---|
| UPS Alarms Present | snmp.ups.AlarmsPresent | The present number of active alarm conditions. |